Collect, repair, and deliver back to site 1 x 6.6kv a ash booster circuit breaker NB: All the works are done in accordance with SANS -, SANS -1, and IEC . The scope of work includes but is not limited to: · Collect the MV vacuum contactor at Hendrina power station. · Strip & assess the contactor for damage(s) · Clean the contactor trolley and replace all the worn-out parts. · Develop a QIP for the contactor · Sandblast the trolley and repaint the trolley with the original color of the contactor · Mount the new unit on the trolley/carriage with new vacuum interrupters and fuses. · Replace the trip coil and the close coil with new ones. · Install the operation counter. · Provide the original manufacturer's datasheet for the contactor. · All technical communications concerning the scope of work to be done via email to above Vacuum contactor ratings: · Service Voltage - 6.6kV · Rated Voltage - 7.2kV · Rated lightning impulse withstand voltage - 95kV · Rated power frequency withstand voltage - 28kV · Rated frequency - 50Hz · Rated current - A · Fuse(s) rating- In = A, Un = 6/12kV · Rated short circuit breaking current- 25kA · Rated peak withstand current - 63kA · Close coil - VDC · Close coil pick up voltage - 82V · Time spread between the poles during closing and opening is less than 4ms · Opening/closing cycles- . The